Danfoss (JIA XING) 6RT psychrometric lab final acceptance

1.Synopsis of the Facility

This facility is used for measuring the capacity of Air-con by air enthalpy method. It also measures various kinds of data including pressure and electric properties of the Air-con. And it consists of indoor side (1 room),outdoor side (1 room), air handling unit, refrigerating machine, airflow meters(Two sets), power panel,computer system and so on.
This facility can not only in accordance with the international standard complete the testing of AC, but also meet the standard AHRI210/240 of the air conditioning SEER/HSPF evaluation. For this purpose, the degradation coefficient (CD) of UUT can be measured by actual tests series.
The lab is designed as safety level EX IIC(Zone 2), capable to performs tests for product which used HC refrigerant such as R290.

2.Definition of the Unit Under Test
  Non-ducted air conditioners and heat pumps:
  Window type Air-con.
  Slip type Air-con.
  Cassette type Air-con.
  Ducted air conditioners
  Units above can with Single speed, two capacity and variable speed component (Indoor fan and/or compressor)
  The indoor unit should be equiped with indoor fan by itself.

3.Capacity : 3~20kW

  Commissioning was completed on Nov 2013, Final acceptance on JAN 2014.

 